PowerGuard commercial system installation instructions
PowerGuard CPM30-1W
Installation
Remove the lid of the unit and securely fit upright against a panel or wall with Fischer or
normal 4mM screws. The 4,5mM mounting holes are accessible through the rectangular
apertures on the four corners of the enclosure. Drill or punch 20mM holes at the bottom of
the enclosure to accommodate glands as required for wiring.
Set Up Instructions
After powering up the system, SW1 active will inhibit its load when overall demand falls
within the backlash range selected on the shed controller. This feature falls away when the
backlash transgression restores and only activates again after a power interruption. This
feature is essential for customers with a compromised electrical supply.
SW2 active responds to phase conscious shed requests, again essential for customers with a
compromised supply. Customers with adequate supply will realise an improved random
shed pattern with SW2 off.
SW3, 4 & 5 set the minimum shed period following a shed request. With these switches off,
the period is 1 minute and increases by 2,5 minutes for each additional binary bit added.
Total shed period is as follows: SW3=3,5; SW4=6; SW3+4=8,5; SW5=11; SW3+5=13,5;
SW4+5=16 and SW3+4+5=18,5 minutes.
SW6, 7 & 8 control the minimum time between accepting shed requests. These switches
together with switches 3,4&5 are essential for air conditioner control to ensure that the
occupant’s comfort levels are not compromised. With SW6,7&8 off, there is no lock-out
interval. SW6=15; SW7=30; SW6+7=45; SW8=60; SW6+8=75; SW7+8= 90 and SW6+7+8=105
minutes.
SW9 & 10 decide on how many CPM30-1W receivers, on average, should respond to a shed
request. For example, if 100 receivers are installed, all set to odds = 50, then approximately
2 units will shed for each shed request. With a total of 10 units, all set to odds = 10,
approximately 1 unit will shed for each shed request. Odds are manipulated such that a
recently shed unit will revert to maximum odds to allow other units to shed before it
responds to the next shed request. With both SW9&10 off, odds= 5; SW9= 10; SW10= 25
and SW9&10= 50. Odds can be decreased within a control grid to favour higher priority
loads or can be increased to protect lower priority loads.